Insulated fixpoint HV 4
PDF sheet
Insulated fixpoint HV 4
CAD Download

Insulated fixpoint HV 4

406,4 mm Insulation 40 mm Shell length 204 mm

Part no. 698400406
EAN/GTIN 4250928441225
Packing unit 1 pcs
Quantity unit pcs
Weight 13,67 kg/pc
Product group 03-698
Price unit 1

Your price

Quantity (pcs):

Product filter:

by Outer pipe diameter [mm]

by Load FY [kN]

by Load FZ [kN]

Application area

Insulated fixpoint mounting of chilled water pipes of steel.

Specification

With natural rubber on front ends, high water vapor diffusion resistance and low thermal conductivity and acc. AGI requirements.

Scope of delivery

2 x half shell with slot for inner and outer split ring, 2 x inner split ring for welding to steel pipe, 4 x outer split ring for fixation on substructure

Material PU
min. temperature resistance -50 °C
max. temperature resistance 105 °C
Density 200 kg/m³
Insulation thickness 40 mm
Outer pipe diameter 406,4 mm
Hole distance S 538 mm
Thermal conductivity 0,037 W/mK
Length shell L 204 mm
Width outer split ring B 567 mm
Recommended base HV4
Load FY 13,6 kN
Load FZ 20,3 kN
Note delivery time on demand