Insulated fixpoint HV 4
PDF sheet
Insulated fixpoint HV 4
CAD Download

Insulated fixpoint HV 4

323,9 mm Insulation 40 mm Shell length 204 mm

Part no. 698400324
EAN/GTIN 4250928441201
Packing unit 1 pcs
Quantity unit pcs
Weight 11,30 kg/pc
Product group 03-698
Price unit 1

Your price

Quantity (pcs):

Product filter:

by Outer pipe diameter [mm]

by load Fy [kN]

by load Fz [kN]

Application area Insulated fixpoint mounting of chilled water pipes of steel
Specification PUR (with natural rubber on front ends)
High water vapor diffusion resistance and low thermal conductivity.
Acc. AGI the requirements
Delivery 2 x half shell with slot for inner and outer split ring
2 x inner split ring for welding to steel pipe
4 x outer split ring for fixation on substructure
Material PU
min. temperature resistance -50 °C
max. temperature resistance 105 °C
Density 200 kg/m³
Insulation thickness 40 mm
Outer pipe diameter 323.9 mm
Hole distance 455 mm
Thermal conductivity 0.037 W/mK
Length shell 204 mm
Width outer split ring 484 mm
Recommended fixpoint bracket<br /> [type] HV4
load Fy 11.1 kN
load Fz 16.8 kN